Combined Over Current and Earth Fault Relay | TM-9000s

 

 

  • Front Panel
  • Tech Data
  • Dimension
  • Wiring
  • Graph
  • Download
TECHNICAL DATA
Measurement True RMS Ampere
Power supply 85 ~ 270 VAC / 100 ~ 340 VDC
16 ~ 36 VDC (model: D24n)
Rated current ../5A, ../1A upon request
Rated frequency 50 / 60 Hz (selectable)
Rated operation level >= 1.10 x (IDMT), >= 1.0 x (DTL)
C.T. burden@5A < 0.5 VA
Tripping contact SPDT 5A / 240 VAC
Weight 520g
Operating temp. 0° C ~ +55° C
Standard IEC : 61000-4-2/4-4/4-5/255-5:1
SETTING RANGE  
Current Setting 20% ~ 200% (1% step) over current
2 ~ 50% (1% step) earth fault
Time setting 0.05 ~ 1.00 (0.01 time multiplier step)
0.05 ~ 20.0 (0.1 sec step)
High-set 20 ~ 2000% (10% step) over current
20 ~ 1000% (10% step) earth fault
High-set time 0.03 ~ 20.0 (0.1 sec step)

Features

- True RMS measurement

- Low set and High set

- Operation hour recording

- Fault / Trip LED indication

- 7-tripping history

- Neutral current display

- THD-I display

- Last 30 min. ampere demand

- Maximum ampere demand

- Selectable 6 IDMT grpahs

- 2 output relays

- 4 output relays *

- 1 programmable digital input *

- RS 485 modbus *

- Dual setting parameters *

- Auto shorting of CT terminals (when unplugged)

- Programmable software lock

- Flush mount

* Available for models with communication type only.