TECHNICAL DATA |
Current Input (•n) |
../5A or ../1A |
Frequency |
Software selectable 50 or 60 Hz |
Burden |
<0.3 VA @ •n |
Output Relay Rating |
SPDT 5A, 250V AC/DC |
Display |
7-Segment LED (3 + 1digit) |
Indication (LEDs) |
x10, pre-alarm, fault, fault start event,
lo / hi trip |
Operating Temp. |
0ºC ~ +55ºC |
Humidity |
56 days at 93%RH, 40ºC non-condensing |
IP Rating |
IP54 (front panel) |
PARAMETER SETTING (Phase OverCurrent) |
|
•p> : lo-set |
2% to 200% (step of 1%) |
TM •p> : lo-set time Multiplier |
0.05 ~ 1.00
(step of 0.01, 5 IDMT + 1 DTL) |
•p> : lo-set trip delay time |
0.03s ~ 20.0s
0.03s ~ 0.10s (step of 0.01s)
0.10s ~ 1.00s (step of 0.02s)
1.0s ~ 20.0s (step of 0.1s) |
•p >> : hi-set |
OFF or 20% ~ 2000%
20% ~ 1000% (step of 10%)
1000% ~ 2000% (step of 100%) |
•p >> : hi-set trip delay time |
0.03s ~ 20.0s (same range as •p>) |
PARAMETER SETTING (Earth Fault) |
|
•e >: lo-set |
2% to 100% (step of 1%) |
TM •e > : lo-set time Multiplier |
0.05 ~ 1.00
(step of 0.01, 5 IDMT + 1 DTL) |
•e > : lo-set trip delay time |
0.03s ~ 20.0s
0.03s ~ 0.10s (step of 0.01s)
0.10s ~ 1.00s (step of 0.02s)
1.0s ~ 20.0s (step of 0.1s) |
•e >> : hi-set |
OFF or 20% ~ 1000% (step of 10%) |
•e >> : hi-set trip delay time |
0.03s ~ 0.5s |