Earth Fault Relay | DP-21

 

 

  • Front Panel
  • Tech Data
  • Dimension
  • Wiring
  • Download
TECHNICAL DATA
Current Input (•n) ../5A or ../1A
Frequency Software selectable 50 or 60 Hz
Burden <0.3 VA @ •n
Output Relay Rating SPDT 5A, 250V AC/DC
Display 7-Segment LED (3 + 1digit)
Indication (LEDs) x10, pre-alarm, fault, fault start event,
lo / hi trip
Operating Temp. 0ºC ~ +55ºC
Humidity 56 days at 93%RH, 40ºC non-condensing
IP Rating IP54 (front panel)
Weight 230 g
PARAMETER SETTING  
•>: lo-set 2% ~ 100% (step of 1%)
•>: lo-set trip delay time 0.03s~20.0s
0.03s~0.10s (step of 0.01s)
0.10s~1.00s (step of 0.02s)
1.0s~20.0s (step of 0.1s)
•>>: hi-set OFF or 20%~1000% (step of 10%)
•>>: hi-set trip delay time fixed @ 30ms

 

Features

- True RMS Measurement with SPARC1 and
DCOI2 Algorithm

- Fundamental Signal Detection3

- Real Time Display of I•n in mA/A

- Fault / lo-set & hi-set Trip LED Indication

- Fault Start Event Recording &
LED Indication + Output4

- Pre-Alarm LED Indication + Output4

- Trip Event Memory
(non-volatile 7 previous records)

- Fault Start Event Memory
(non-volatile 4 previous records)

- Programmable Relay Output contact for K2

- Last Trip Elapsed Time (up to 99days)

- Software Lock to Prevent Unauthorized Setting

- Complies with IEC-60255-26 Standards

- External Plug-in Module for :-
A-01s (RS-485 MODBUS RTU) isolated type

  DELAB Scientific | Copyrights © 2013 @ Delab Scientific. All rights reserved.